国产美女视频免费一级_亚洲一级做a爰片久久毛片无码_白丝制服被啪到喷水在线_黄色网站立即观看_九色91无码一区_国产精品毛片大胆_男人添女欧美精品_中文字幕亚洲无线码毛片_日本三级香港三级乳网址下载_视频二区日韩在线

Language

British Standard Cables

Position:Home > Products > Cable series > British Standard Cables
318A to BS 6004(Formerly BS 7919)
Specification
Description
Download

Cable Construction

圖片1.png圖片2.png

Anealed copper conductor

Stranding to BS 6360 CL-5 or IEC 60228 CL-5

- PVC core insulation TI 4 to EN 50363-3-1(formerly BS 7655-3-1)

- Green/Yellow grounding (3 conductors and above)

- PVC outer jacket Type 10 to BS7655-4-2

- Yellow or blue


Application and Description

318A to BS 6004(Formerly BS 7919) cables are designed to withstand severe external temperatures and will remain flexible at temperatures down to -40°C. Making them particularly suitable for outdoor applications and for use where flexibility is required at sub zero temperatures. At normal temperatures the cable is very flexible, offering some of the characteristics usually found in elastomeric cables.,


Technical Characteristics

Working voltage: 300/500 volts

Test voltage: 2000 volts

Flexing bending radius: 6xOverall diameter

Static bending radius: 4xOverall diameter

Flexing temperature: -5o C to +70o C

Static temperature: -40o C to +70o C

Short circuit temperature: +160o C

Flame retardant: IEC 60332.1

- Insulation resistance: 20 MΩxkm