Position:Home > News > Industry NewsYJV22 Copper Core Cable Load Flow, Power Cable Load Flow
0.6/1kV Crosslinking Sheath Power Cable Main Technical Parameters Load Flow
NO | Type | Specification | Rated Voltage | Cable calculation | long term loading current (A) | |||
Outer diameter | In the air | Buried in the soil | ||||||
kV | mm | Copper | Aluminum | Copper | Aluminum | |||
1 | 3×35 | 0.6/1 | 23.1 | 144 | 113 | 167 | 122 | |
2 | 3×50 | 0.6/1 | 25.8 | 176 | 135 | 198 | 149 | |
3 | 3×70 | 0.6/1 | 29.1 | 221 | 171 | 243 | 180 | |
4 | 3×95 | 0.6/1 | 32.6 | 270 | 207 | 288 | 216 | |
5 | YJV22 | 3×120 | 0.6/1 | 35.8 | 315 | 243 | 329 | 248 |
6 | 3×150 | 0.6/1 | 41.2 | 360 | 279 | 369 | 279 | |
7 | 3×185 | 0.6/1 | 45.3 | 419 | 324 | 419 | 320 | |
8 | 3×240 | 0.6/1 | 49.9 | 495 | 387 | 486 | 369 | |
9 | 3×300 | 0.6/1 | 54.9 | 572 | 446 | 549 | 419 | |
10 | 4×35 | 0.6/1 | 26.4 | 144 | 113 | 167 | 122 | |
11 | 4×50 | 0.6/1 | 30.2 | 176 | 135 | 198 | 149 | |
12 | 4×70 | 0.6/1 | 34.2 | 221 | 171 | 243 | 180 | |
13 | 4×95 | 0.6/1 | 38.9 | 270 | 207 | 288 | 216 | |
14 | 4×120 | 0.6/1 | 45.6 | 315 | 243 | 329 | 248 | |
15 | 4×150 | 0.6/1 | 47.9 | 360 | 279 | 369 | 279 | |
16 | 4×185 | 0.6/1 | 52.3 | 419 | 324 | 419 | 326 | |
17 | 4×240 | 0.6/1 | 58.1 | 495 | 387 | 486 | 369 | |
18 | 4×300 | 0.6/1 | 63.7 | 572 | 446 | 549 | 419 | |
19 | 3×35+1×16 | 0.6/1 | 26.2 | 144 | 113 | 167 | 122 | |
20 | 3×50+1×25 | 0.6/1 | 30.0 | 176 | 135 | 198 | 149 | |
21 | 3×70+1×35 | 0.6/1 | 33.9 | 221 | 171 | 243 | 180 | |
22 | YJLV22 | 3×95+1×50 | 0.6/1 | 38.6 | 270 | 207 | 288 | 216 |
23 | 3×120+1×70 | 0.6/1 | 45.2 | 315 | 243 | 329 | 248 | |
24 | 3×150+1×70 | 0.6/1 | 47.6 | 360 | 279 | 369 | 279 | |
25 | 3×185+1×95 | 0.6/1 | 51.9 | 419 | 324 | 419 | 326 | |
26 | 3×240+1×120 | 0.6/1 | 57.7 | 495 | 387 | 486 | 369 | |
27 | 3×300+1×150 | 0.6/1 | 63.3 | 572 | 446 | 549 | 419 |